Restaurants, food trucks & commercial kitchens

Kitchen hood fire suppression in CalgaryInspected, tagged and booked for next time.

A kitchen hood fire suppression system must be inspected every 6 months under NFPA 96 and NFPA 17A. In Calgary that inspection typically costs $275 to $750, depending on hood size, and takes about two hours. Defense Fire Protection installs, inspects, repairs and replaces these systems, tags them, and books your next visit so you never miss a Calgary Fire Department check.

  • Manufacturer-trained on the brand you have
  • Written report with photos of any deficiency
  • Next 6-month inspection booked automatically
4.9 on Google24/7 emergency serviceEst. 2022 · 40+ yrs combined experienceBrands we sell & service
  • Kidde
  • Badger
  • Amerex
  • Buckeye
  • ProTex II
  • CaptiveAire
  • Autocall
NFPA 96 · NFPA 17A · NFPA 10 · CAN/ULC-S536
Buckeye kitchen fire suppression cylinders and release module installed by Defense Fire Protection

What we do for Calgary kitchens

We handle the whole life of a kitchen hood suppression system, from the first install to every six-month service after it.

  • 6-month inspections, tagged and reported, with your next visit booked automatically.
  • New system installs for new restaurants, renovations and line changes, coordinated with your contractor and electrician.
  • Replacement of outdated systems that are not UL 300 compliant or have been modified with mismatched parts.
  • Repairs and recharges after a discharge, a failed inspection or a deficiency notice.
  • Fire alarm and gas valve tie-ins so the system shuts off fuel and signals the alarm panel when it fires. See fire alarm inspection for the alarm side.

Running a food truck or trailer? See food truck fire suppression.

How does a kitchen hood suppression inspection work in Calgary?

A technician checks the whole system against your current cook line, replaces the parts that must be replaced every service, tests that it fires and shuts off fuel, then tags it. Most restaurants take about two hours.

  1. System and hood assessment

    We confirm the system brand and model, check nozzle coverage against your current appliances, and verify all components are listed for that system.

  2. Links, nozzles and cartridges

    We replace fusible links, clean and cap nozzles, and inspect or replace the cartridge and agent cylinder as required.

  3. Activation and shut-off test

    We test the detection line, manual pull station, gas valve shut-off and electrical and alarm connections, where applicable.

  4. Tag, report and next booking

    You get a new service tag, a written report with photos of any deficiencies, and your next 6-month inspection on the calendar.

Recent kitchen suppression work

Amerex KP wet chemical cylinder and mechanical release module installed in a Calgary restaurantDefense Fire Protection technician servicing Buckeye kitchen fire suppression cylindersTwo Buckeye kitchen fire suppression cylinders and release module installed above a restaurant hood

Parts we check on every Calgary kitchen suppression system

Agent cylinder & pressure gauge

We confirm the gauge is in the green, check the valve assembly and gauge shield, and track the 12-year hydrostatic test date.

Control head & micro switch

We trip the releasing device to prove it fires, signals the fire alarm panel and shuts down equipment.

Fusible links & detection line

New fusible links at the correct temperature rating every service, with the cable, conduit and pulley elbows checked for grease and binding. Why the link rating matters →

Nozzles & nozzle caps

Appliance, plenum and duct nozzles are cleaned, re-capped and re-aimed against your current appliance line-up. Moved an appliance? Read this →

Gas shut-off valve

We confirm the mechanical or electric gas valve closes on discharge, and reset it.

Pull station & K-class extinguisher

We test the remote manual pull station and confirm your K-class extinguisher and placard are within 9.1 m of the cooking line. Extinguisher service →

What does Alberta require for kitchen hood suppression?

A system listed to UL 300 or ULC/ORD-C1254.6, inspected and maintained every 6 months by a technician certified on that manufacturer's system, tied to the building fire alarm if there is one, with records kept on site.

  • Inspection and maintenance every 6 months by a technician certified by that system's manufacturer, or holding the approved SAIT certificate.
  • Systems must meet UL 300 or ULC/ORD-C1254.6. Sprinkler heads and CO2 systems under the hood don't count.
  • If the building has a fire alarm, the suppression system must trigger it on discharge.
  • Inspection records stay on site, and none can be destroyed within 5 years.

Cooking donair, gyro or shawarma? Vertical rotisseries have their own rules: see donair and shawarma cooker fire suppression in Alberta.

Source: Alberta STANDATA 23-FCI-004/23-BCI-009 and National Fire Code – 2023 Alberta Edition. More in our FAQ →

Why can't you mix suppression system brands?

Because kitchen suppression systems are tested and listed as a complete unit from one manufacturer. On a recent Calgary inspection we found a Kidde agent cylinder connected to a Badger control head. Those parts are not listed to work together, so the system cannot be certified and may not discharge correctly in a fire.

If your last company swapped in "whatever fit," we will document it and quote the fix: matching parts or a full replacement.

Read the full Kidde + Badger case →

Buckeye kitchen fire suppression system installed beside a restaurant exhaust hood in Calgary

Signs your kitchen suppression system needs service now

The service tag is more than 6 months old

You moved, added or swapped cooking appliances

Nozzle caps are missing or nozzles are greasy

You received a deficiency notice from the fire department or your insurer

The system discharged, even partially. What to do right now →

You bought a restaurant and don't know the system's history

Book an inspection

Kitchen suppression brands we sell, install and service in Calgary

Authorized distributor. Compare the systems →

Kitchen hood fire suppression FAQ (Calgary)

How often does a kitchen hood suppression system need to be inspected in Calgary?

Every 6 months. NFPA 96 and NFPA 17A require semi-annual inspection by a qualified technician, and the Calgary Fire Department can ask to see a current tag. Defense Fire Protection books your next inspection automatically.

How much does a kitchen hood suppression inspection cost in Calgary?

Typically $275 to $750 before GST, depending on hood size, the number of systems and cylinders, and which parts are due. Fusible links are replaced at every service, and we give a written quote before any repairs. Get a price range in 60 seconds →

What is included in a kitchen hood suppression inspection?

Replacing fusible links, cleaning and capping nozzles, testing activation, and replacing cartridges as needed. Where applicable we also test the detection line, manual pull station, gas valve shut-off and electrical connections, then tag the system and send a report.

Do I have to close my restaurant for the inspection?

No. Most inspections take about two hours, and cooking appliances only need to be off while we test. We can book before opening or between services.

Can I use parts from different suppression manufacturers?

No. Each kitchen suppression system is listed as a complete unit from one manufacturer. Mixing parts, such as a Kidde cylinder with a Badger control head, voids the listing, fails inspection, and can stop the system from working in a fire. Read the full case →

My system is old. Do I need to replace it?

If it is not UL 300 compliant, or parts are no longer available, replacement is usually required. Older dry-chemical systems were not designed for modern high-temperature cooking oils. We will tell you on the first visit and quote the replacement.

How much does a new kitchen suppression system cost in Calgary?

A new kitchen hood suppression system in Calgary typically costs $6,000 to $12,000 installed, depending on hood length and appliances (most 8 to 14 ft hoods land between $7,200 and $9,700). That usually includes stamped engineered drawings, the permit and the extinguishers; the electrical scope is done by others. We provide a written quote after reviewing drawings or a site visit. Get a price range in 60 seconds →

What should I do if my suppression system goes off?

Make sure everyone is safe and the fire department has cleared the scene, then call us at (403) 807-5822. The system must be cleaned, recharged and reset by a technician before you cook again. Step-by-step: what to do after a discharge →

Is hood cleaning part of the suppression inspection?

No. Hood and duct cleaning is a separate NFPA 96 service done by a hood-cleaning company. We can schedule our inspection right after your cleaning so nozzles and links are fresh.

Never miss an inspection date

Tell us when your tag expires. We'll remind you a month before, so the fire inspector is never the one who tells you.

Book your hood inspection

Tell us what you have. A real person replies within one business day, usually the same day. Prefer to talk? Call (403) 807-5822.

  • Written quote before any work
  • Photos of every deficiency
  • We book your next inspection and remind you

Call (403) 807-5822 or get a price range in 60 seconds →

We'll text and email you about this request (msg & data rates may apply; reply STOP to opt out). We never share your details. Privacy policy