The short answer
Yes. Under the National Fire Code – Alberta Edition, a service company that finds a fire alarm defect the owner won’t or can’t fix must notify the fire department and the owner in writing. The Calgary Fire Department’s letters to building owners state that it expects these reports within 10 days of the inspection, and that an annual certificate alone isn’t accepted as proof of inspection.
Many building owners don’t realize that a fire alarm inspection isn’t just between them and their service company. Under the Alberta fire code, the Calgary Fire Department expects to hear about deficiencies, and it doesn’t accept a certificate on its own as proof of inspection.
When does a fire alarm company have to report to the fire department?
When it finds equipment that is inoperative or defective and the owner is unwilling or unable to fix it. The National Fire Code – Alberta Edition says that if the person maintaining fire protection equipment (extinguishers, suppression systems, fire alarms) finds a device or system inoperative or defective, and the owner won’t or can’t correct it, they must notify the fire department and the owner in writing.
The Calgary Fire Department’s letters to building owners and property managers state what that means in practice: fire alarm service companies are required to report systems with deficiencies, and the CFD expects them to be reported within 10 days of the inspection. A Fire Safety Codes Officer then contacts the owner to confirm repairs are done, and asks for documentation.
What’s the difference between a deficiency and a recommendation?
Deficiencies must be fixed; recommendations are optional. Deficiencies are problems that must be corrected under the fire code. Recommendations are your service company’s professional suggestions to improve protection. If you do act on a recommendation, it has to be done to code, it may need a permit, and once it’s part of the system it has to be maintained at every future inspection. Our price estimator shows typical ranges for common deficiency repairs.
Is a fire alarm certificate enough proof of inspection in Calgary?
No. The CFD has said it does not accept annual fire alarm certificates alone as proof of inspection. The standard (CAN/ULC-S536) calls for a detailed report showing the building address, inspection date, testing standard, system status, deficiencies, and recommendations on a separate page. That report has to be kept on site for two years and be available to fire inspectors.
What this means for you: fix deficiencies quickly, ideally before the 10-day reporting window closes, and keep the full inspection report on site, not just a certificate. If your current provider only hands you a certificate, ask for the full report. If you have an Autocall panel, see Autocall fire alarm service.
Quick answers
Does my fire alarm company report me to the fire department?
In Calgary, yes: service companies are required to report systems with unrepaired deficiencies, and the Calgary Fire Department’s letters to owners say it expects reports within 10 days of the inspection.
How long do I keep fire alarm inspection reports?
At least two years, on site, available for the fire inspector.
Sources
- National Fire Code – 2019 Alberta Edition, Division B, Sentence 6.1.1.3.(2)
- Calgary Fire Department, Fire Marshal’s letters to building owners and property managers on fire alarm maintenance and annual certificates
- CAN/ULC-S536, Inspection and Testing of Fire Alarm Systems
This article is general information, not a code ruling: your local fire department has the final say.