Fire extinguishersHow often do I need to service my fire extinguishers?

Defense Fire Protection service vans that bring extinguisher service to your site

The short answer

Every fire extinguisher needs an inspection and a new tag every year. On top of that, stored-pressure dry chemical extinguishers get 6-year maintenance, and every extinguisher gets a hydrostatic test: every 12 years for dry chemical, and every 5 years for K-class (wet chemical), water and CO₂ units.

Fire extinguishers serviced and tagged by Defense Fire Protection

Fire extinguishers are the first line of defence in any commercial or industrial space, but only if they have the right rating for the room and they work when someone pulls the pin. NFPA 10, the standard for portable fire extinguishers, sets three kinds of service. Here is what each one is and when it is due.

1. Every year: the annual inspection

A certified technician checks that each extinguisher still holds its pressure, that the pin and tamper seal are in place and the pin can be pulled, that the hose and nozzle are clear, and that the shell has no damage or corrosion. It also checks that the extinguisher is mounted where it should be and suits the hazard in that room. Each unit gets a new tag with the date, which is what the fire inspector looks for. See our annual inspection and tagging service.

2. Every 6 years: maintenance (stored-pressure dry chemical)

Six years after the manufacture date, or after the last hydrostatic test, a stored-pressure dry chemical extinguisher is emptied and examined inside. The technician checks the cylinder, rebuilds the valve head and replaces the rubber parts that dry out over time, such as O-rings and valve seals, then refills and repressurizes it.

3. Every 5 or 12 years: the hydrostatic test

A hydrostatic test fills the cylinder with water and pressurizes it well above its normal working pressure, to make sure the shell won't leak, bulge or rupture. Dry chemical extinguishers are hydro tested every 12 years; K-class, water and CO₂ extinguishers every 5 years. More on hydrostatic testing and 6-year maintenance.

Where to find the dates: the manufacture date is stamped on the cylinder or printed on the label, and the last 6-year maintenance or hydrostatic test is on the service label, usually on the back of the extinguisher. If you can't read it, bring the extinguisher to our showroom at 6560 2 St SE, Calgary, AB T2H 1J4 or ask us on your next visit.

Quick answers

How often does a fire extinguisher need to be inspected?

Every year, by a certified technician, who tags it with the date. Staff should also glance at each extinguisher regularly to make sure it is in place, charged and not blocked.

How often does a fire extinguisher need a hydrostatic test?

Every 12 years for dry chemical extinguishers, and every 5 years for K-class (wet chemical), water and CO₂ extinguishers.

What is 6-year maintenance on a fire extinguisher?

For stored-pressure dry chemical extinguishers: the unit is emptied and examined inside, the valve is rebuilt with new seals, then it is refilled and repressurized.

Sources

  • NFPA 10, Standard for Portable Fire Extinguishers

This article is general information, not a code ruling: your local fire department has the final say.

Want a technician to look at yours?

Call (403) 807-5822

Not sure when your extinguishers are due?

Send a photo of the tag or the service label. A technician tells you what's due and books it in.

  • Written quote before any work
  • Photos of every deficiency
  • We book your next inspection and remind you

Or get a price range in 60 seconds →

Add email, address, notes or photos (optional)

We'll text you about this request, and email you if you add your email (msg & data rates may apply; reply STOP to opt out). We never share your details. Privacy policy